9   Cause of Transmission value in the Update Key Change Reply message

Created: 14 Jan 2025

Status: Approval (Editoral)

Part: Part 5-7 (2013, Edition 1)

Links:

Page: 26

Clause: 7.3.11

Paragraph: Cause of Transmission

Issue

The possible Cause of Transmission values listed for the Update Key Change Reply message in monitor direction include the following values:

<44>:= unknown type identification
<45>:= unknown cause of transmission
<46>:= unknown common address of ASDU

The above values are not possible since this message is sent by the controlled station only.

Proposal

Correct the list of the Cause of Transmission in monitor direction by removing the following values:

<44>:= unknown type identification
<45>:= unknown cause of transmission
<46>:= unknown common address of ASDU

Discussion Created Status
The proposed comment resolution was approved. 14 Mar 25 Approval (Editoral)
In Par. 7.3.1 after Fig. 11, the causes of transmissions 44, 45 and 46 shall be removed.

Paragraph 7.3.11 shall be corrected as indicated in the attached picture
14 Mar 25 Discussion (red)
Moved to discussion 14 Mar 25 Discussion (red)
Accepted 21 Feb 25 Accepted

 